Page 17: Lients

Advertising
background image

BACnet Server for AcquiSuite

Page 17 of 52

CVS:bacnet/Documentation/BACnet_Users_Guide.doc

2.2.4 Case Study: “Consumption Only” Option at 9600 Baud

If your application requires only “energy” (kWh) data, the AcquiSuite’s “consumption only” option is worth

considering.

In this case study, the AcquiSuite’s “consumption only” option has been turned on for those meters which

support the option (compare this table to

the above

).

This causes the AcquiSuite to only log the “energy” points (kWh) rather than all points, reducing the data

to be logged and allowing a quicker data refresh interval.

Contact Obvius for details about whether a particular meter supports “consumption only” mode.

2.3 Maximum BACnet Clients

Obvius recommends a maximum of 128 simultaneous BACnet clients. “Reads” are satisfied from

cache. The achievable data refresh interval is typically limited by the AcquiSuite’s Modbus RS485

bandwidth, number and type of meters.

If writing (to relays) via BACnet, Obvius recommends a maximum of 8 simultaneous “writers.” Writes

are not cached; each write will result in a Modbus write to the relay device.