background image

BACnet Server for AcquiSuite

Page 18 of 52

CVS:bacnet/Documentation/BACnet_Users_Guide.doc

2.4 Minimum APDU_Timeout

Obvius recommends BACnet clients use a minimum APDU_Timeout of 6 seconds.

If writing to relays, BACnet clients should use an APDU_Timeout which is greater than the actual data

refresh interval, which depends on the system configuration. This may be estimated from the above

tables or measured using

BACnet

à Device List à show: [stats] tab

.

2.5 Supported Relay Types

The BACnet Server for AcquiSuite supports the following Modbus relay devices.

· Obvius, A8812 Internal I/O,

· Obvius, A8332-8F2D Flex I/O

· Advantec, Adam 4068 and 4069

· Acromag, 902MB

· Coyote DataComm, Rio-9F

· Benjamin Electric, Power Panel Plus

2.6 Fail Safe Logic Design

If your application involves controlling relays, please consider fail safe logic design. Please see

Symptom: Relays Turn On When They Shouldn’t

for a brief discussion of the issues.