How the acquisuite signals communications failures – Obvius BACnet User Manual

Page 47

Advertising
background image

BACnet Server for AcquiSuite

Page 47 of 52

CVS:bacnet/Documentation/BACnet_Users_Guide.doc

Stale Time >= (APDU_Timeout * Number_of_APDU_Retries)

8.7.2 How the AcquiSuite Signals Communications Failures

The BACnet Server for AcquiSuite will signal communications failures by updating the Status_Flags and

Reliability properties of each data point’s Analog Input or Binary Value object, and by setting the

System_Status property of each Device Object.

These properties may be monitored by the Controller. For instance, on the Tridium JACE, these

properties may be “added” in the same way you would discover and “add” the Present_Value of an input

(see below). These properties can then be used to “gate” your control logic.

Advertising