Read Reqs / Errs: # of read errors vs. total reads. A “read error” is counted if, when answering a

BACnet RP or RPM request, the meter’s data was not already cached and we failed to get a

response from the meter in 65 seconds.

·

Write Reqs / Errs: # of write errors vs. total writes. A “write error” is counted if we either timeout

or get an error response when writing to a backend device.

·

I/O Response Time, Avg: Moving average of response-time from this meter (reads or writes).

Note: This differs from a meter's RTT (displayed in the AcquiSuite’s Modbus

à

Device List

à

[stats] tab) in that it includes the effect of the overall load on the AcquiSuite, the communications

to all other meters, logging activity, etc.

·

I/O Response Time, Worst = worst-case (peak) response-time from this meter, over the last 63

requests (reads or writes).

6.2.5 show: [all]

The [all] tab shows all fields in a single, very wide table. This is useful for cutting-and-pasting the table

into other apps.

6.3 BACnet Discover

→ Objects

The Discover and Device List pages include an “objects” link next to each BACnet device. When clicked

this queries and displays the object list of the local or remote BACnet device. For example: