iNsTallaTioN

Continued

CONNECTING TO GAS SUPPLY

WARNING: This appliance re-

quires a 45° male flare fitting 5/8"-

18 UNF (Unified National Fine

Thread) inlet connection and the

flexible gas line provided.

WARNING: A qualified ser-

vice person must connect fire-

place to gas supply. Follow all

local codes.

WARNING: Never connect

natural gas fireplace to private

(non-utility) gas wells. This

gas is commonly known as

wellhead gas.

IMPORTANT:

For natural gas, check gas line

pressure before connecting fireplace to gas line.

Gas line pressure must be no greater than 14" of

water. If gas line pressure is higher, heater regula-

tor damage could occur.

CAUTION: Never connect pro-

pane/LP fireplace directly to the

propane/LP supply. This fireplace

requires an external regulator

(not supplied). Install the external

regulator between the fireplace

and propane/LP supply.

For propane/LP units, the installer must supply

an external regulator. The external regulator will

reduce incoming gas pressure. You must reduce

incoming gas pressure to between 11" and 14" of

water. If you do not reduce incoming gas pressure,

fireplace regulator damage could occur. Install

external regulator with the vent pointing down

as shown in Figure 13. Pointing the vent down

protects it from freezing rain or sleet.

Propane/LP
Supply Tank

External Regulator

Figure 13 - External Regulator With Vent

Pointing Down

Vent Pointing Down

CAUTION: Use only new,

black iron or steel pipe. Inter-

nally-tinned copper tubing may

be used in certain areas. Check

your local codes. Use pipe of

1/2" or greater diameter to allow

proper gas volume to fireplace.

If pipe is too small, undue loss

of volume will occur.

Installation must include an equipment shutoff

valve, union and plugged 1/8" NPT tap. Locate

NPT tap within reach for test gauge hook up. NPT

tap must be upstream from heater (see Figure 14,

page 14).
IMPORTANT:

Install equipment shutoff valve

in an accessible location. The equipment shutoff

valve is for turning on or shutting off the gas to

the appliance.

Check your building codes for any special re-

quirements for locating equipment shutoff valve

to fireplaces.

Apply pipe joint sealant lightly to male NPT

threads. This will prevent excess sealant from

going into pipe. Excess sealant in pipe could result

in clogged fireplace valves.

WARNING: Use pipe joint

sealant that is resistant to liquid

petroleum (LP) gas.