Air for combustion and ventilation, Ventilation air, Continued – Desa CGMFP User Manual

Page 8

Advertising
background image

www.desatech.com

119315-01A

8

The space in the example is a confined space because

the actual Btu/Hr used is more than the maximum

Btu/Hr the space can support. You must provide ad-

ditional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoin-

ing room. If the extra space provides an unconfined

space, remove door to adjoining room or add

ventilation grills between rooms. See Ventilation

Air From Inside Building.

B. Vent room directly to the outdoors. See Ventila-

tion Air From Outdoors.

C. Install a lower Btu/Hr fireplace, if lower Btu/Hr

size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr

the space can support, the space is an unconfined space.

You will need no additional fresh air ventilation.

WARNING: If the area in which

the heater may be operated is

smaller than that defined as

an unconfined space or if the

building is of unusually tight

construction, provide adequate

combustion and ventilation air

by one of the methods described

in the National Fuel Gas Code,

ANSI Z223.1/NFPA 54 Section 5.3

or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside building

This fresh air would come from an adjoining un-

confined space. When ventilating to an adjoining

unconfined space, you must provide two permanent

openings: one within 12" of the ceiling and one

within 12" of the floor on the wall connecting the

two spaces (see options 1 and 2, Figure 4). You

can also remove door into adjoining room (see

option 3, Figure 4). Follow the National Fuel Gas

Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for

Combustion and Ventilation for required size of

ventilation grills or ducts.

aiR FoR CoMBUsTioN

aND VENTilaTioN

Continued

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or

ducts. You must provide two permanent openings:

one within 12" of the ceiling and one within 12"

of the floor. Connect these items directly to the

outdoors or spaces open to the outdoors. These

spaces include attics and crawl spaces. Follow the

National Fuel Gas Code, ANSI Z223.1/NFPA 54,

Section 5.3, Air for Combustion and Ventilation for

required size of ventilation grills or ducts.
IMPORTANT:

Do not provide openings for inlet

or outlet air into attic if attic has a thermostat-

controlled power vent. Heated air entering the attic

will activate the power vent.

Figure 4 - Ventilation Air from Inside

Building

Or

Remove

Door into
Adjoining

Room,

Option 3

Ventilation Grills

Into Adjoining Room,

Option 2

12"

12"

Ventilation

Grills

into

Adjoining

Room,

Option 1

Figure 5 - Ventilation Air from Outdoors

Outlet

Air

Ventilated

Attic

Outlet

Air

Inlet

Air

Inlet Air

Ventilated

Crawl Space

To

Crawl

Space

To Attic