Component assembly 14, Component assembly – Scotsman MAR1400 User Manual

Page 14

Advertising
background image

Component Assembly

1. Install the ice chute.
2. Route the bin thermostat from its shipping

position on the control box to the ice chute.
3. Install the bin thermostat bulb in the ice chute.

MAR SPLIT UNIT - REFRIGERANT PIPING

CONNECTION
Fitting sizes:

Liquid Line

Suction Line

3/8"

5/8"

Note: Connect the proper size tubing according to

the length of run. Runs longer than 10 feet will

require larger diameter tubing than these

connection sizes.
The MAR unit is shipped with a small holding

charge of R-404A. Recover this charge before

connecting the refrigeration tubing.
Take extreme care to keep refrigeration tubing

clean and dry prior to installation.
Following procedure should be followed:
a) Do not leave dehydrated compressor or

filter-drier open to the atmosphere any longer than

it is absolutely necessary. (One or two minutes

maximum suggested).
b) Use only refrigeration grade copper-tubing,

properly sealed against contamination.
c) Permanent suction line filter and liquid line

filter-driers are recommended in all field installed

systems.
d) When brazing refrigerant lines, an inert gas

must be passed through the line at low pressure to

prevent scaling and oxidation inside the tubing.

Dry nitrogen is preferred.
e) Line connections to vibration eliminators must

be made with silver solder alloy. Arrange that

refrigerant lines run along the walls and ceilings

and be supported at intervals frequent enough to

keep tubing straight and firmly in place. In all

cases the tubing should be run horizontally and

vertically with neat looking bends of as perfect

radius as possible.
The liquid line is not critical regarding its slope and

position, but the suction line must be installed so

the tubing will drain toward the compressor.

After all lines are connected, the entire system

must be leak tested.
The complete system should be pressurized to no

more than 11 atm (170 PSIG) with a trace of R-22

refrigerant and dry nitrogen for leak testing with an

electronic type leak detector.
For pressurizing, evacuating and charging the

system, two service valves are necessary; one

should be in the Suction Line at the inlet side of

suction filter and one should be in the Liquid Line

at the outlet side of filter dryer.
The two Service Valves, if properly capped, can be

left permanently in the system. Connection should

be 3/8" or 1/2" size.
WATER PIPING CONNECTIONS (PLUMBING)
The MAR is supplied with float valve that maintains

the water level in drum reservoir at the height

required for fresh water operation or if required, for

sea water operation. The water inlet line connects

directly to the float valve line fitting which is 3/4"

hose coupling thread, (copper tubing is not

recommended for sea water supply).
Note: An adapter fitting to go from 3/4” hose

coupling thread to 3/8” male flare is packed

inside the MAR unit.
Make sure to use a hand shut-off valve close

enough to MAR unit and a proper kind and size of

filter strainer.
Incoming water goes through the float reservoir

first and then to drum basin.
The drain water line should be shaped adequately

to drain by gravity any water passing through it.
Water drain fitting from float reservoir requires a 20

m/m I.D. (3/4” ID) water hose.
All plumbing connections should be made in

accordance with local plumbing codes.

MAR1400 & MAR2000

December 2000

Page 14

Advertising
This manual is related to the following products: