Service Diagnosis

The Service Diagnosis Section is for use in aiding

the servicemen in diagnosing a particular problem

for pin-pointing the area in which the problems

lines, thus an ever available reference for proper

corrective action.

The following chart lists corrective actions for the

causes of known symptoms of certain problems

that can occur in the ice making refrigeration

system.

MAR1400 & MAR2000

December 2000

Page 32

SYMPTOM

POSSIBLE CAUSE

CORRECTION

Lo-refrigerant press.

Incorrect refrigerant

suction pressure

Add refrigerant to raise suction

pressure.

Raise head press. Control setting.

Moisture in system. Overcharge of oil

in system.

Check moisture indicator and

remove charge and drier. Replace

& recharge the system.

Not enough refrigerant.

Check for refrigerant leak.

Lo-water level.

Intermittent water supply or too low

water pressure.

Water shut-off valve closed. Check

and clean water strainer.

The compressor runs but the

unit

does not make ice.

Drive motor gear reducer

inoperative.

Check. Repair or replace.

V-belt loose or broken

Check. Repair or replace.

Key may sheared.

Check. Repair or replace.

Gear reducer with one gear

stripped - off.

Check. Repair or replace.

Pulley loose on motor shaft.

Check. Repair or replace.

Water not entering reservoir.

Check and clean. Water float

valve

to be cleaned.

Excessive Hi-pressure

Hi-pressure unit operation

Check cooling water at

condenser.Condenser tube

clogged-up. Water regulating valve to

be re-adjusted.