Location Consideration

WARNING - MAR SCALE ICE MAKERS are not

designed for outdoor installations where air

temperature falls below 5EC (40EF) or may

exceed 40EC (100EF)
Operating a machine with an unacceptable

configuration will void the refrigeration system

warranty.
For installation on board of fishing vessels, the

location for the condensing unit is generally the

engine room, while the evaporator unit can be

permanently placed in some area of the

deck-house or, if it is not too cold (not below 5EC

or 40

o

F.), inside the fish and ice hold.

If the MAR unit will be mounted to a fabricated

stand, it must be adequately fastened to it.
The stand must also be sturdy so it does not cause

excessive vibration and must be able to be

securely fastened to the wall or to the floor.
Placement of the MAR unit must take into

consideration where the ice is discharged and

what type of container (ice storage bin or walk-in)

will be used.
REFRIGERANT LINES
The diameter of refrigerant lines going from

condensing unit to evaporator unit and back must

be of adequate size in relation to tubing length.
The table below show the recommended sizes of

refrigerant lines:
Note: The tubing connections at the MAR unit are

3/8” liquid and 5/8” suction.

Insulate any lines that will be exposed to

temperatures that will be below freezing for

extended periods of time.
Follow straight line routing, when possible,

however pitch the suction line 2 cm per meter or

¾” per yard.
Do not restrict the liquid line. Bends and fittings

should be the minimum necessary as they can

increase the resistance to the fluid flow.
If using a semi-hermetic compressor, the use of

vibration absorbers near the condensing unit will

help to reduce condensing unit vibration traveling

into the lines.
Because the appearance of an installation is

important, the piping should be put-in as neatly as

possible.
For best sound absorption, it is best to put-in two

absorbers in each line, one vertically and one

horizontally.
For evacuation and charging operations two

service valves must be provided. One on the liquid

line and one on the suction line.
A drier and a sight glass should be installed in the

liquid line at the condensing unit.

MAR1400 & MAR2000

December 2000

Page 9

Length of Tubing Run

Suction Line

Liquid Line

4 to 15 meters (11 to 50 feet)

18 mm ID (3/4” OD)

12 mm ID (1/2” OD)

Less than 3 meters (10 feet)

14 mm ID (5/8” OD)

14 mm ID (3/8” OD)