Condensing Unit Component Control Devices

The scale-ice maker refrigeration system must

have certain safety devices and controls in order to

fully protect it, however an excess of automatic

controls and protections may complicate the

situation.
In order to help the installer to decide with which

controls to use, a description of typical controls

and their positive and negative points is listed

below.
High Pressure Control
Strongly recommended for a condensing unit. Set

to values shown on tech. spec.
Lo Pressure Control
Recommended for a condensing unit. Very

important because in case of refrigerant leaks at

the evaporator, it prevents the operation of the

machine when the evaporator is in a vacuum.

Operating the evaporator in a vacuum could draw

into the system water from the drum reservoir.

Vacuum could also cause air inflow through the

compressor crank-shaft seal.
However, it may trip-out at system start-up and if

the suction operating pressure is very close to the

cut out point, it may trip out then as well.