Service Diagnosis

REFRIGERATION SYSTEM

MAR101 & MAR121

December 2000

Page 33

SYMPTOM

POSSIBLE CAUSE

CORRECTION

Unit will not run.

Blown fuse.

Replace fuse and check for cause

of blow fuse.

Loose electrical connection.

Check wiring.

Switch in OFF position.

Turn switch to ON.

Inoperative master switch.

Replace switch.

Spout switch cut-out.

Check ice chute arrangement.

Excessive noise

Misaligned V-belt.

Align V-belt.

Gear reducer loose on frame.

Tighten.

Drive motor end-play or worn

bearings.

Repair or replace.

Excessive vibration.

Ice formation underneath

blade -

frictioning against rotating drum.

Remove blade and melt-up ice

formation. Lower water level to

correct value.

Making wet ice

Surrounding air temperature

above

40EC (100EF)

Correct or move unit to cooled

location.

Under-or-over-charge of refrigerant. Re-charge with proper amount.

Closed AEV.

Adjust valve for correct refrigerant

flow.

Faulty compressor valve plate.

Repair or replace.

Low ice production.

Loss of refrigerant,under

or overcharge of refrigerant

Check and recharge with proper

amount of refrigerant.

Plugged condenser water tubes

Clean condenser.

Low water level in the reservoir.

Check float valve operation.

Overcharge of oil in system.

Check at oil sight glass.

Lower to 1/2

sight glass.

Water pump out of operation.

Replace water pump.

Spray bar clogged.

Clean spray bar.