Dial up with hardware signalling – Westermo TD-32 User Manual

Page 48

Advertising
background image

48

6178-2203

Dial up with hardware signalling

Dial up can be made by applying an external signal to the DTR-pin in the RS-232/V.24 contact.
A typical application is an alarm signal from a PLC or another relay contact.

The modem reacts on the first rising edge which means that one pulse is sufficient.
The signal level should be in compliance with the RS-232/V.24 standard. If only a relay contact
is available the DSR-pin will provide a suitable voltage.

The modem does not have a redialling function. If necessary this must be handled by other
equipment connected. We advise the DCD signal to be used as a control indicating whether
connection was made or not.

AT&B1

Dial-up using DTR.

AT&D3

Hang-up if DTR goes low.

AT&Z0=nn

The number to dial, nn, is stored in memory position 0.

Please also refer to ”To use minicall”, as the minicall and the dial-up with
hardware signalling can be used together.

External signal