Cooling system – H3C Technologies H3C SR6600-X User Manual
Page 15

5
Substance
Concentration limit (particles/m
3
)
NOTE:
Dust particle diameter ≥ 5 μm
The equipment room must also meet strict limits on salts, acids, and sulfides to eliminate corrosion and
premature aging of components, as shown in
.
Table 5 Harmful gas limits in an equipment room
Gas Max.
(mg/m
3
)
SO
2
0.2
H
2
S 0.006
NH
3
0.05
Cl
2
0.01
Cooling system
Fan trays of the routers are hot swappable and support automatic fan speed adjustment. To ensure good
ventilation, the following requirements must be met:
•
Leave at least 10 cm (3.94 in) of clearance at the inlet and outlet air vents.
•
The installation site has a good cooling system.
Figure 2 Airflow through the SR6608-X chassis
NOTE:
An SR6604-X router uses the same airflow system as an SR6608-X router.