5  Mounting Location

SMA Solar Technology AG

14

TCS-JP-IA-en-10

Installation Manual

Minimum Clearances for the Transformer Compact Station

Figure 7: Minimum clearances for the Transformer Compact Station

:$51,1*

Fire hazard due to overheating of cables
Differing cable lengths lead to overheating of the cables. Excessive heat can result in cable fires. Death or serious injury

due to fire can result.

• All line conductors from the inverter to the Transformer Compact Station must be of the same length.
• The cable length between the connection points must not exceed 15 m.

Position

Designation

A

Lateral minimum clearance

B

Minimum clearance at the front of the Transformer Compact Station

C

Minimum clearance at the back of the Transformer Compact Station

TCS 500SC-JP

TCS 630SC-JP

TCS 800SC-JP

A

600 mm

600 mm

600 mm

B

1,400 mm

1,600 mm

1,700 mm

C

1,700 mm

1,900 mm

2,000 mm