2 grounding the high-voltage transformer – SMA TCS 500SC-JP User Manual

Page 28

Advertising
background image

7  Electrical Connection

SMA Solar Technology AG

28

TCS-JP-IA-en-10

Installation Manual

Procedure:

1. Install the ground electrodes in accordance with the applicable regulations.
2. Ensure that the required grounding resistance is achieved.
3. Clean the contact surfaces (see Section 7.5, page 25).
4. Mount the grounding cable to the grounding busbar using screw, nut and washers.
5. Tighten the bolted connection at the grounding connection (torque: 12 Nm).
6. Check that the grounding cable is correctly connected.
7. Connect the grounding cables to the grounding busbar.
8. Connect the grounding cables to the ground electrode.

7.6.2 Grounding the High-Voltage Transformer

Figure 15: Position of the grounding bolt on the high-voltage transformer

Procedure:

1. Clean the contact surfaces (see Section 7.5, page 25).
2. Connect the grounding cable to the grounding bolt of the high-voltage transformer with screw and washers

(torque: 37 Nm).

3. Check that the grounding cable is correctly connected.

Position

Designation

A

Screw

B

Spring washer

C

Fender washer

D

Grounding cable