8  Commissioning

Installation Manual

TCS-JP-IA-en-10

39

8.4 Checking the AC Low Voltage at the Low-Voltage Power Switch

1. Check the low voltage for the right-hand rotating magnetic field. Correct if necessary.
2. Measure the low voltage between the line conductors and log in the commissioning report.

– L

1

- L

2

– L

1

- L

3

– L

2

- L

3

☑ The low voltage is within ± 5 V of the nominal voltage of the inverter.

✖ Does the low voltage vary from the nominal voltage of the inverter by more than ± 5 V?

• Disconnect the high-voltage transformer from voltage sources.
• Have a duly authorized person adjust the conversion ratio of the high-voltage transformer by the tap changer.

☑ The tap changer clicks into place.

• Proceed to Step 2.