SMA TCS 500SC-JP User Manual

Page 30

Advertising
background image

7  Electrical Connection

SMA Solar Technology AG

30

TCS-JP-IA-en-10

Installation Manual

7.7.2 Installing the Connection between the High-Voltage Transformer and the

High-Voltage Connection Busbars

Figure 17: High-voltage connection area of the Transformer Compact Station

Requirements:

☐ The Transformer Compact Station must be anchored to the support surface (see Section 6.3, page 16).
☐ The grounding of the high-voltage transformer must be connected (see Section 7.7.1, page 29).
☐ The high-voltage transformer must be connected to the low-voltage power switch (see Section 7.7.1, page 29).

Procedure:

1. Clean the contact surfaces (see Section 7.5, page 25).
2. Lead the cables through the protection against contact.
3. Connect the cables coming from the high-voltage connection busbars to the high-voltage side of the high-voltage

transformer with screws, nuts and washers (torque: 37 Nm). Pay attention to the colored labeling of the cables.

4. Ensure that the connections are correctly made.
5. Slide the protection against contact over the connection points.

Position

Designation

A

High-voltage connection area

Advertising
This manual is related to the following products: