3 installing the contact thermometer connections – SMA TCS 500SC-JP User Manual

Page 31

Advertising
background image

SMA Solar Technology AG

7  Electrical Connection

Installation Manual

TCS-JP-IA-en-10

31

7.7.3 Installing the Contact Thermometer Connections

Figure 18: Contact thermometer of the high-voltage transformer

Requirements:

☐ The Transformer Compact Station must be anchored to the support surface (see Section 6.3, page 16).
☐ The grounding of the high-voltage transformer must be connected (see Section 7.7.1, page 29).
☐ The high-voltage transformer must be connected to the low-voltage power switch (see Section 7.7.1, page 29).
☐ The high-voltage transformer must be connected to the high-voltage connection area (see Section 7.7.2, page 30).

Procedure:

1. Using a cross-head screwdriver, unscrew the four screws (M4) of the cover.
2. Remove the cover with seal and safely store it along with the screws.
3. Insert the cable into the contact thermometer sideways.
4. Connect the cable to the terminal of the contact thermometer with screws, nuts and washers in accordance with the

circuit diagram (torque: 1.57 Nm).

5. Ensure that the connection is correctly made.
6. Mount the seal and cover and tighten all four screws using a cross-head screwdriver (torque: 1.4 Nm).

Position

Designation

A

Contact thermometer

Advertising