9 technical data, Technical data – SMA AUTOMATIC SWITCH BOX XL User Manual

Page 46

Advertising
background image

Technical Data

SMA Solar Technology AG

46

AS-BOX-XL-IEN094410

Installation Guide

9 Technical Data

General

Consumer load connection

PV system connection

Number of phases

3-phase

Nominal voltage

3 x 230 V / 400 V or

3 x 240 V / 415 V

Nominal frequency

50 Hz

Number of Sunny Backup

6 / 9 / 12 x SBU 5000

Mounting type

Standing on a base

Permitted grid structure on grid side

TN-C

Permitted grid structure on load side

TN-S

Number

1 (three-phase)

Nominal current

3 x 160 A

Nominal power

110 kW

Diameter of bolt clamp for connecting N and PE

8 mm

Diameter of the screws on the fuse element for connecting
L1, L2, and L3

8 mm

Maximum torque of bolt clamp

6 Nm … 12 Nm

Maximum torque of fuse element

14 Nm

Maximum cable cross section suitable for connection

70 mm²

Maximum fuse plug

160 A

Fuses

NH00

Number

1 (three-phase)

Nominal current

3 x 160 A

Nominal power

110 kW

Diameter of bolt clamps

8 mm

Maximum torque of bolt clamp

6 Nm … 12 Nm

Maximum cable cross section suitable for connection

70 mm²

Fuses

none