Technical Data
SMA Solar Technology AG
46
AS-BOX-XL-IEN094410
Installation Guide
9 Technical Data
General
Consumer load connection
PV system connection
Number of phases
3-phase
Nominal voltage
3 x 230 V / 400 V or
3 x 240 V / 415 V
Nominal frequency
50 Hz
Number of Sunny Backup
6 / 9 / 12 x SBU 5000
Mounting type
Standing on a base
Permitted grid structure on grid side
TN-C
Permitted grid structure on load side
TN-S
Number
1 (three-phase)
Nominal current
3 x 160 A
Nominal power
110 kW
Diameter of bolt clamp for connecting N and PE
8 mm
Diameter of the screws on the fuse element for connecting
L1, L2, and L3
8 mm
Maximum torque of bolt clamp
6 Nm … 12 Nm
Maximum torque of fuse element
14 Nm
Maximum cable cross section suitable for connection
70 mm²
Maximum fuse plug
160 A
Fuses
NH00
Number
1 (three-phase)
Nominal current
3 x 160 A
Nominal power
110 kW
Diameter of bolt clamps
8 mm
Maximum torque of bolt clamp
6 Nm … 12 Nm
Maximum cable cross section suitable for connection
70 mm²
Fuses
none