4 Option Components
YASKAWA ELECTRIC
TOBP C730600 43C 1000-Series Option SI-N3 Installation Manual
11
■
Power-Up Diagnostics
An LED test is performed each time the drive is powered up. The initial boot sequence may
take several seconds. The option is successfully initialized when the LEDs complete the
diagnostic LED sequence. The LEDs then assume operational conditions shown in
.
Table 4 Power-Up Diagnostic LED Sequence
Sequence
Module Status (MS)
Network Status (NS)
Time (ms)
1
Green
OFF
250
2
Red
OFF
250
3
Green
Green
250
4
Green
Red
250
5
Green
OFF
-