Option mac id, Option baud rate, Eds files – Yaskawa 1000 Series Drive Option - DeviceNet Installation User Manual

Page 22: 5 installation procedure

Advertising
background image

5 Installation Procedure

22

YASKAWA ELECTRIC

TOBP C730600 43C 1000-Series Option SI-N3 Installation Manual

Option MAC ID

Parameter F6-50, MAC ID Setting 0 to 64

The option MAC ID is set with drive parameter F6-50. MAC ID settings between 0~63 are

considered valid MAC IDs; setting 64 indicates a network-settable MAC ID.
The option reads the MAC ID value from F6-50 upon power-up and upon a network reset.

Option Baud Rate

The option supports standard baud rates of 125 kbps, 250 kbps, and 500 kbps.

Table 5 Parameter F6-51 Baud Rate Setting

Auto Baud Rate Sensing (F6-51 = 4)

Setting parameter F6-51 to 4 enables automatic baud rate detection and allows the option to

automatically determine the baud rate of the DeviceNet network.

Note: Auto baud rate sensing is valid only when there is more than one node physically on the

DeviceNet network segment. If the auto baud rate sensing fails to detect the baud rate, the drive

digital operator will display “bUS” and the option LEDs will be OFF (NS) and solid green (MS).

EDS Files

To facilitate network implementation, obtain an EDS file from one of the following websites

depending on your region:
US: http://www.yaskawa.com
Europe: http://www.yaskawa.eu.com
Japan: http://www.e-mechatronics.com
Other areas: contact a Yaskawa representative.

Description

Value

125 kbps

0

250 kbps

1

500 kbps

2

Programmable from Network

3

Auto Detect

4