6 Related Parameters

YASKAWA ELECTRIC

TOBP C730600 43C 1000-Series Option SI-N3 Installation Manual

25

F6-60

(3DB)

DeviceNet Voltage

Scaling

Sets the scaling factor for the Voltage Monitor in the

DeviceNet Object Class 2A

Note: Used in the AC/DC Drive Object

Default: 0

Min: -15

Max: 15

F6-61

(3DC)

DeviceNet Time Scaling

Sets the scaling factor for the Time Monitor in the

DeviceNet Object Class 2A hex

Note: Used in the AC/DC Drive Object

Default: 0

Min: -15

Max: 15

F6-62

(3DD)

DeviceNet Heartbeat

Interval

Sets the heartbeat interval

Note: Used in the Identity Object

Default: 0

Min: 0

Max: 10

F6-63

(3DE)

DeviceNet Network

MAC ID

(Read only)

Actual MAC address

Note: Used in the DeviceNet Object

Default: 0

Min: 0

Max: 63

U6-98

(7F8)

Previous Option Fault

Displays previous faulted status.

0: No fault

1: Option failure

2: PLC in idle state

3: Force fault

1000: Network power loss

1001: Connection timeout

1002: Duplicate MAC ID

1003: Bus-off

Note: Used in option faults

Range: 0 to 3;

1000 to 1003

U6-99

(7F9)

Current Option Fault

Displays the most recent fault status.

0:No fault

1: Option failure

2: PLC in idle state

3: Force fault

1000: Network power loss

1001: Connection timeout

1002: Duplicate MAC ID

1003: Bus-off

Note: Used in option faults

Range: 0 to 3;

1000 to 1003

<1> To start and stop the drive with the DeviceNet master device using serial communications, set b1-02 to 3 or set the

Net Control bit in the assemblies or Control Supervisor Object. To control the frequency reference of the drive via

the master device, set b1-01 to 3 or set the Net Reference bit in the assemblies or AC/DC object.

<2> Setting F6-01 or F6-03 to 3 will allow the drive to continue to operate after detecting a fault. When allowing the

drive to continue operation after fault detection, be sure to take proper safety measures such as installing an

emergency stop switch.

<3> Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01 determines

whether the value is read as the torque limit value (d5-01 = 0) or read as the torque reference value (d5-01 = 1).

This value is read as the torque limit in CLV/PM.

<4> Default setting specifies that the torque reference or torque limit is to be provided via network communications

(F6-06 = 1). The motor may not rotate if no torque reference or torque limit is supplied from the PLC.

<5> All MAC addresses must be unique.

<6> Setting unavailable values will initialize Polled Consuming Assembly (PCA) and Polled Producing Assembly

(PPA).

<7> Cycle power for setting changes to take effect.

No.

(Addr.

Hex)

Name

Description

Values