6 Related Parameters

24

YASKAWA ELECTRIC

TOBP C730600 43C 1000-Series Option SI-N3 Installation Manual

F6-08

(36A)

Reset Communication

Parameters

Determines which F6-†† and F7-†† parameters are reset

to default values when initializing the drive using A1-03.

0: Do not reset parameters

1: Reset parameters

Default: 0

Range: 0, 1

F6-50

(3C1)

<5>

<7>

DeviceNet MAC ID

Selects the drive MAC address

Note: Used in the DeviceNet Object

Default:

<8>

Min: 0

Max: 64

F6-51

(3C2)

<7>

DeviceNet

Communication Speed

DeviceNet communication speed

0: 125 kbps

1: 250 kbps

2: 500 kbps

3: Programmable from network

4: Auto detect

Note: Used in the DeviceNet Object

Default:

<9>

Range: 0 to 4

F6-52

(3C3)

<6>

DeviceNet PCA Setting I/O Polled Consuming Assembly data instance

Note: Used in the Connection Object

Default: 21

Min: 0

Max: 255

F6-53

(3C4)

<6>

DeviceNet PPA Setting

I/O Polled Producing Assembly data instance

Note: Used in the Connection Object

Default: 71

Min: 0

Max: 255

F6-54

(3C5)

<7>

DeviceNet Idle Mode

Fault Detection

When detection is enabled and idle messages are detected,

the option will set Run and Frequency to 0.

0: Detection enabled

1: No detection

Default: 0

Range: 0, 1

F6-55

(3C6)

DeviceNet Baud Rate

Monitor

(Read only)

DeviceNet actual communication speed

0: 125 kbps

1: 250 kbps

2: 500 kbps

Note: Used in the DeviceNet Object

Default: 0

Range: 0 to 2

F6-56

(3D7)

DeviceNet Speed

Scaling

Sets the scaling factor for the Speed Monitor in the

DeviceNet Object Class 2A hex

Note: Used in the AC/DC Drive Object

Default: 0

Min: -15

Max: 15

F6-57

(3D8)

DeviceNet Current

Scaling

Sets the scaling factor for the Output Current Monitor in the

DeviceNet Object Class 2A hex

Note: Used in the AC/DC Drive Object

Default: 0

Min: -15

Max: 15

F6-58

(3D9)

DeviceNet Torque

Scaling

Sets the scaling factor for the Torque Monitor in the

DeviceNet Object Class 2A hex

Note: Used in the AC/DC Drive Object

Default: 0

Min: -15

Max: 15

F6-59

(3DA)

DeviceNet Power

Scaling

Sets the scaling factor for the Power Monitor in the

DeviceNet Object Class 2A hex

Note: Used in the AC/DC Drive Object

Default: 0

Min: -15

Max: 15

No.

(Addr.

Hex)

Name

Description

Values