8 Troubleshooting

8

Troubleshooting

Drive-Side Error Codes

Table 8

lists the various fault codes related to the option. Refer to the drive Technical

Manual for further details on the fault codes.

Faults

Both bUS (Option Communication Error) and EF0 (External Fault Input from the option)

can appear as either an alarm or as a fault. When a fault occurs, the digital operator ALM

LED remains lit. When an alarm occurs, the digital operator ALM LED flashes.
Check the following items first when an error code occurs on the drive:

• Communication cable connections.

• Make sure the option is properly installed to the drive.

• Operation status of the controller program and controller CPU.

• Did a momentary power loss interrupt communications?

Table 8 Fault Displays, Causes, and Possible Solutions

Digital Operator Display

Fault Name

bUS

Option Communication Error
The connection was lost after establishing initial communication.

Only detected when the run command frequency reference is assigned to the option

(bl-01 = 3 or bl-02 = 3).

Cause

Possible Solution

Master controller (PLC) has

stopped communicating

Check for faulty wiring.

Correct any wiring problems.

Communication cable is not

connected properly

A data error occurred due to

noise

• Counteract noise in the control circuit wiring, main circuit lines, and ground wiring.

• If a magnetic contactor is the noise source, install a surge absorber to the contactor

coil.

• Use cables recommended by Yaskawa or another type of shielded line. Ground the

shield on the controller side and on the option side.

Option is damaged

If there are no wiring problems and the fault continues to occur, replace the option.

Network power loss

The power on the DeviceNet network cable is 0.

Verify power is available between option terminals V+ (red) and V- (black).

Connection timeout

The option Expected Packet Rate (EPR) timer timed out.

Make sure that EPR time is set properly.

Duplicate MAC ID

The option MAC ID and at least one other node have the same MAC ID.

Verify F6-50 is set properly. All MAC IDs must be unique.