10 specifications – Yaskawa 1000 Series Drive Option - DeviceNet Installation User Manual

Page 35

Advertising
background image

YASKAWA ELECTRIC

TOBP C730600 43C 1000-Series Option SI-N3 Installation Manual

35

10 Specifications

10

Specifications

Table 11 Option Specifications

Items

Specifications

Model

SI-N3

SI-N3 Supported

Messages

• Group 2 Server (UCMM capable).

• Explicit Messages: Fragmentation is supported. Up to 32 bytes can be input and output.

• Polled I/O Messages: Fragmentation is not supported. Up to 8 bytes can be input and output.

• Faulted Node Recovery / Offline Connection Set Messages / Automatic Device Replacement

(ADR).

• Change of State Message (COS). COS can be used as an I/O Input Assembly.

I/O Assembly

Instance

Input: 17 types (4~8 bytes)

Output: 18 types (4~8 bytes)

DeviceNet

Specification

Conformance Level 19: Passed

DeviceNet Profile AC Drive

Input Power

Voltage: 11~25 Vdc

Current: 40 mA

Connector Type

5-pin open-style screw connector

Physical Layer

Type

Isolated Physical Layer

CAN transceiver + photocoupler

MAC ID Setting

Programmable from drive keypad or network:

MAC ID 0 to 63

Communications

Speed/Baud Rate

Programmable from drive keypad or network:

• 125/250/500 kbps

• Auto Baud Rate

• Idle Mode Detect

• Heartbeat

Ambient

Temperature

-10 °C to +50 °C (14 °F to 122 °F)

Humidity

95% RH or lower with no condensation

Storage

Temperature

-20 °C to +60 °C (-4 °F to 140 °F) allowed for short-term transport of the product

Area of Use

Indoor (free of corrosive gas, airborne particles, etc.)

Altitude

1000 m (3280 ft.) or lower

Advertising