5 Installation Procedure
28
YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual
4.
Connect the ground wire (G) to the ground terminal (A) using one of the remaining
provided screws (C). Connect the other end of the ground wire (G) to the ground
terminal and installation hole on the option using the last remaining provided screw
(C) and tighten both screws to 0.5 to 0.6 Nxm (4.4 to 5.3 in lbs).
Figure 13
Figure 14 Connecting the Ground Wire
5.
Wire the communication cables.
Note: Separate communication cables from main circuit wiring and other electrical lines.