9 Troubleshooting

9

Troubleshooting

Drive-Side Error Codes

Drive-side error codes appear on the drive digital operator. Causes of the errors and

corrective actions are listed in

Table 12

. For additional error codes that may appear on the

drive digital operator, refer to the drive Technical Manual.

Faults

Both bUS (Option communication error) and EF0 (External fault input from the option) can

appear as an alarm or as a fault. When a fault occurs, the digital operator ALM LED remains

lit. When an alarm occurs, the ALM LED flashes.
If communication stops while the drive is running, use the following questions as a guide to

help remedy the fault:

• Is the option properly installed?

• Is the communication line properly connected to the option? Is it loose?

• Is the controller program working? Has the controller/PLC CPU stopped?

• Did a momentary power loss interrupt communications?

Table 12 Fault Displays, Causes, and Possible Solutions

LED Operator Display

Fault Name

bUS

Option Communication Error.

• After establishing initial communication, the connection was lost
• Only detected when the run command or frequency reference is assigned to the option

(b1-01 = 3 or b1-02 = 3)

Cause

Possible Solution

Master controller (PLC)
has stopped
communicating

• Check that power is supplied to the PLC
• Check that PLC is not in program mode

Communication cable is
not connected properly

• Check for faulty wiring
• Correct any wiring problems

A data error occurred due
to noise

• Check the various options available to minimize the effects of noise
• Counteract noise in the control circuit, main circuit, and ground wiring
• If a magnetic contactor is identified as a source of noise, install a surge absorber to the

contactor coil

• Make sure the cable used meets the Modbus TCP/IP requirements
• Make sure the option ground wire is connected between option FE terminal and the

drive ground terminal connected to earth ground

Option is damaged

If there are no problems with the wiring and the error continues to occur, replace the
option.