9 Troubleshooting

44

YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual

Duplicate IP Address

The option shares IP Address with at least one other node.
Check the setting value of F7-03 and F7-04.

LED Operator Display

Fault Name

EF0

Option Card External Fault
The alarm function for an external device has been triggered.

Cause

Corrective Action

An external fault is being
sent from the upper
controller (PLC)

• Remove the cause of the external fault
• Reset the external fault input from the PLC device

Problem with the PLC
program

Check the program used by the PLC and make the appropriate corrections.

PLC is in the Idle Mode.

• Set the PLC to the Run Mode.
• Set the drive parameter F6-54 to 0 (Enabled) not to detect errors while the PLC is in the

Idle Mode.

LED Operator Display

Fault Name

oFA00

Option Card Connection Error (CN5-A)
Option is not properly connected.

Cause

Possible Solution

Non-compatible option
connected to the drive

Connect an option that is compatible with the drive.

LED Operator Display

Fault Name

oFA01

Option Card Fault (CN5-A)
Option is not properly connected.

Cause

Possible Solution

Problem with the
connectors between the
drive and option

Turn the power off and check the connectors between the drive and option.

LED Operator Display

Fault Name

oFA03

Option Card Error (CN5-A)
Option self-diagnostics error.

Cause

Possible Solution

Option hardware fault

Replace the option.