6 related drive parameters – Yaskawa Modbus TCP/IP Installation User Manual

Page 33

Advertising
background image

6 Related Drive Parameters

YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual

33

F7-11
(3EF)

<7>

Gateway Address
3

Sets the static/fixed Gateway address.
Parameter F7-11 sets the third most significant octet.

Default: 1
Range: 0 to 255

F7-12

(3E0)

<7>

Gateway Address
4

Sets the static/fixed Gateway address.
Parameter F7-12 sets the fourth most significant octet.

Default: 1
Range: 0 to 255

F7-13

(3F1)

Address Mode at
Startup

Selects how the option address is set.
0: Static

<6>

1: BOOTP
2: DHCP

Default: 2
Range: 0 to 2

F7-14

(3F2)

Duplex Mode
Selection

Selects duplex mode setting.
0: Half duplex forced
1: Auto-negotiate duplex mode and communication speed
2: Full duplex forced

Default: 1
Range: 0 to 2

F7-15

(3F3)

<8>

Communication
Speed Selection

Sets the communication speed.
10: 10 Mbps
100: 100 Mbps

Default: 10
Range: 10, 100

F7-16

(3F4)

Communication
Loss Time-out

Sets the time-out value for communication loss detection in tenths
of a second. A value of 0 disables the connection time-out.
Example: An entered value of 100 represents 10.0 seconds.

Default: 0
Min.: 0
Max.: 300

H5-11

(43C)

Communications
ENTER Function
Selection

Select the function for the ENTER command that saves parameter
data to the drive.
0: Parameter changes are activated when ENTER command is
written
1: Parameter changes are activated immediately without use of
ENTER command

Default: 1
Range: 0, 1

<1> To start and stop the drive with the option master device using serial communications, set b1-02 to 3. To control

the drive frequency reference via the master device, set b1-01 to 3.

<2> If F6-01 is set to 3, the drive will continue to operate when a fault is detected. Take safety measures, such as

installing an emergency stop switch.

<3> A1000: Enabled in CLV, AOLV/PM, and CLV/PM control modes (A1-02 = 3, 6, or 7). When enabled, d5-01

determines whether the value is read as the Torque Limit value (d5-01 = 0) or read as the Torque Reference value

(d5-01 = 1). In CLV/PM, this value is read as the Torque Limit.

Z1000: Enabled in OLV/PM control modes (A1-02 = 5). When enabled, d5-01 determines whether the value is

read as the Torque Limit value (d5-01 = 0) or read as the Torque Reference value (d5-01 = 1). In V/f, this value

is read as the Torque Limit.

<4> The setting specifies that the Torque Reference or Torque Limit is to be provided via network communications

(F6-06 = 1). The motor may rotate if no torque reference or Torque Limit is supplied from the PLC.

<5> Cycle power for setting changes to take effect.

<6> If F7-13 is set to 0, then all IP Addresses (F7-01 to F7-04) must be unique.

<7> Set F7-01 to F7-12 when F7-13 is set to 0.

<8> Set F7-15 when F7-14 is set to 0 or 2.

No.

(Addr. H)

Name

Description

Values

Modbus_IM_E_conditional.fm 33 ページ 2012年11月5日 月曜日 午後4時32分

Advertising
This manual is related to the following products: