9 Troubleshooting

46

YASKAWA ELECTRIC TOBP C730600 57B 1000-Series Option SI-EM3 Installation Manual

Minor Faults and Alarms

LED Operator Display

Fault Name

oFC00

Option Card Connection Error (CN5-C)
Non-compatible option is connected.

Cause

Possible Solution

Non-compatible option
connected to the drive.

Connect the correct option to CN5-A.

LED Operator Display

Fault Name

oFC02

Option Card Fault (CN5-C)
Option flash write mode.

Cause

Possible Solution

Options AI-A3 or DI-A3
are connected to the
CN5-B port with an
option connected to CN5-
A.

• Only one type of AI-A3, DI-A3 or SI-†† option can be connected to the drive.
• The SI-EM3 option can only be connected to CN5-A

LED Operator Display

Minor Fault Name

CALL

Serial Communication Transmission Error
Communication is not established.

Cause

Possible Solution

Minor Fault

(H2-†† = 10)

Communication wiring is
faulty, there is a short
circuit, or improper
connection

Check for wiring errors:

• Correct the wiring
• Remove ground shorts and reconnect loose wires

YES

Programming error on the
master side

Check communications at start-up and correct programming errors.

Communication circuitry
is damaged.

• Perform a self-diagnostics check
• Replace the drive if the fault continues to occur