The Drive Maximum Torque function sets or dynamically changes the maximum forward and
reverse torque value used by the drive. This control is only available when A2-01 = 3: flux
vector control mode. The forward and reverse torque values are equal when this function is
used.


2.3.3 Accel / Decel


The Accel / Decel function allows the acceleration and deceleration rates to be dynamically
adjusted. The change may be calculated using the following equations when the input is fixed.

Accel Time = (Input 19 x C1-01) / 10000
Decel Time = (Input 19 x C1-02) / 10000

When the input is 100.00% or 10000 the accel / decel rate will be C1-01 and C1-02.


2.3.4 Drive

Output

(contact and transistors)


Drive Output functions provide control to the three multi-function outputs. When the value
connected to the input exceeds the associated P2 parameter level the output will close. It will
open when the input drops below the set level.

Function

Information

Setup

Contact Output 9

Connects terminal 9 to 10

H2-01 = 40: CONNECTION 80, P2-07: Output 9 Level

Trans Output 25

Sinks terminal 25 to 27

H2-02 = 41: CONNECTION 81, P2-08: Output 25 Level

Trans Output 26

Sinks terminal 26 to 27

H2-03 = 42: CONNECTION 82, P2-09: Output 26 Level



2.3.5 Monitor / Analog Output



Monitor functions provide a means to monitor values within a configuration. They can be used
at any time. Monitor functions do not require setup. The value input into a monitor is divided by
10, to increase the range of the monitor’s display.

Figure 2.3.3

Accel/

Decel

19

Figure 2.3.4

Drive

Output 41

81

Drive

Output 40

80

Drive

Output 42

82

Figure 2.3.5

U1-54

Monitor

94

U1-53

Monitor

93

U1-52

Monitor

92

U1-51

Monitor

91

Drive

Analog

Output 51

U1-50

Monitor

90

Drive

Analog

Output 50

U1-56

Monitor

96

U1-57

Monitor

97

U1-58

Monitor

98

U1-59

Monitor

99

U1-55

Monitor

95