Date: 07/01/04, Rev: 04-07

Page 23 of 27

TM.G5SW.015

Scale Multiplier
P1-08 = 0

P1-08

Scale

Multiplier

B B B B


The Scale Multiplier number is multiplied times the value of input 60. Refer to section 2.2.5.

Scale Divisor
P1-09 = 0

P1-09

Scale

Divisor

B B B B


The Scale Divisor is the number divided into the product of the scale multiplication. Refer to
figure 2.2.5.

Scale Bias
P1-10 = 0

P1-10

Scale

Bias

B B B B


The Scale Bias is the number that will be added to the value of the scale calculation to offset the
value of output 61 up or down. Refer to section 2.2.5.

Max Pulses In
P2-01 = 30720

P2-01

Max

Pulses

Input

B B B B


The Max Pulses In is the number that equals the input pulse rate per second that will result in
100 % inverter output. Refer to section 2.1.4.
Example: 30720 = (1800 rpm X 1024 encoder pulses per rev) / 60 sec (30720 is the default)

MOP Rate / Sec
P2-02 = 0.00 %

P2-02

MOP Rate / Second

B

B

B

B


The MOP Rate / Sec sets the rate of MOP change for output 25. This number will be added to
or subtracted from the current value of output 25 when the multi-function input assigned to 82

Setting Range:

-9999 to 9999

Factory Default:

0

Modify During Run:

Yes

Modbus Address:

0587H

Setting Range:

-9999 to 9999

Factory Default:

0

Modify During Run:

Yes

Modbus Address:

0588H

Setting Range:

-9999 to 9999

Factory Default:

0

Modify During Run:

Yes

Modbus Address:

0589H

Setting Range:

0 to 65535

Factory Default:

30720

Modify During Run:

Yes

Modbus Address:

0590H

Setting Range:

0.01 to 100.00 %

Factory Default:

0.00 %

Modify During Run:

Yes

Modbus Address:

0591H