Wiring grounding – Yaskawa V74X Drives User Manual

Page 20

Advertising
background image

20

Wiring
Grounding

Section 4

• The Drive must be solidly grounded using the main circuit ground terminal .
• If Drive is installed in a cabinet with other equipment, ground leads for all equipment should be connected to a

common low-impedance ground point within the cabinet.

• The supply neutral should be connected to the ground point within the cabinet.
•

Select appropriate ground wire size from Table 1-1.

•

Make all ground wires as short as practical.

•

NEVER ground the Drive in common with welding machines, or other high power electrical equipment.

•

Where several Drives are used, ground each directly to the ground point (see Figure 1-2). DO NOT FORM A
LOOP WITH THE GROUND LEADS.

•

When connecting a motor to the Drive’s output terminals, include a separate ground wire. Attach ground wire
solidly to motor frame and to Drive’s ground terminal .

•

When using armored or shielded cable for connection between Drive and motor, solidly connect armor or shield
to motor frame, and to the Drive’s ground terminal .

Figure 1-2. Correct Ground Connection

CORRECT

CORRECT

NOT

ACCEPTABLE

IG.V7.01_new format.qxd:IG.V7.01_new format.qxd 8/21/07 2:24 PM Page 20