Drive Parameter Listing

(n059-n069)

Section 8

PARA-

SETTING RANGE

SETTING

FACTORY

USER

PARA.

METER

NAME

(AND UNITS)

INCREMENT

SETTING

SETTING

REF.

14: During auto restart

Multi-Function Output

15: During undervoltage

n059

Selection 3

16: During reverse run

(Terminals P2 & PC)

17: During speed search

1

2

18: Serial Comm. Controlled
19: PID feedback loss
20: Frequency Reference Loss Detect (N.O.)

``

21: Overheat Pre-alarm OH3 (N.O.)

n060

Analog Frequency Reference

0 to 255

1 (%)

100

Gain (term. FR to FC) (Note 4)

5.8

n061

Analog Frequency Reference

-100 to 100

1 (%)

0

Bias (term. FR to FC) (Note 4)

n062

Analog frequency reference
filter time constant

0.00 to 2.00

0.01 (sec)

0.10

(term. FR to FC) (Note 4)

n064

Frequency Reference Loss

0:

No Detection

1

0

5.33

Detection

1:

Continue to run at 80% of max. frequency

n065

Monitor Output

0:

Analog monitor output

1

0

5.17

Selection

1:

Pulse monitor output

0:

Output frequency (10V = 100% Fmax)

1:

Output Current (10V = 100% drive
rated current)

2:

DC Bus Voltage

n066

Multi-function Analog Output

(10V = 400 VDC [800 VDC])

(Terminals AM & AC)

3:

Motor Torque

1

0

5.17

(10V = Motor rated torque)

4:

Output Power
(10V = Drive Capacity kW)

5:

Output Voltage 10V = n012 (voltage max)

6:

Frequency Reference

n067

Analog Monitor Gain (Note 4)

0.00 to 2.00

0.01

1.00

n068

Analog Frequency Reference

-255 to 255

1%

100

Gain (CN2, Voltage Ref Input)

n069

Analog Frequency Reference

-100 to 100

1%

0

5.32

Bias (CN2, Voltage Ref Input)