Drive parameter listing (n070-n079), Drive parameters - continued – Yaskawa V74X Drives User Manual

Page 42

Advertising
background image

Drive Parameter Listing
(n070-n079)

Section 8

PARA-

SETTING RANGE

SETTING

FACTORY

USER

PARA.

METER

NAME

(AND UNITS)

INCREMENT

SETTING

SETTING

REF.

Analog Frequency Reference

n070

Filter Time Constant

0.00 to 2.00

0.01 s

0.10

(CN2, Voltage Ref Input)

n071

Analog Frequency Reference

-255 to 255

1%

100

Gain (CN2, Current Ref Input)

n072

Analog Frequency Reference

-100 to 100

1%

0

5.32

Bias (CN2, Current Ref Input)

Analog Frequency Reference

n073

Filter Time Constant

0.00 to 2.00

0.01 s

0.10

(CN2, Current Ref Input)

n074

Pulse Train Frequency

-255 to 255

1%

100

Reference Gain

n075

Pulse Train Frequency

-100 to 100

1%

0

5.11

Reference Bias

n076

Pulse Train Frequency Ref-

0.00 to 2.00

0.01 s

0.10

erence Filter Time Constant

0:

Multi-Function analog input disabled

1:

Aux. Frequency reference

n077

Multi-Function Analog

2:

Frequency gain

0

1

Input Selection

3:

Frequency bias

4:

Voltage bias

n078

Multi-Function Analog Input

0:

0 - 10V

1

0

5.32

Signal Selection

1:

4 - 20 mA

n079

Multi-Function Analog Input

0 to 50

1%

10

Bias Setting