Peripheral

Devices

Section 5

Figure 1-3. Customer Connection Diagram For Isolation Transformers, Input Reactors, Input RFI Filters,

DC Reactors, Output Reactors and Output RFI Filters

ISOLATION

TRANSFORMER

INPUT

REACTOR

INPUT

RFI FILTER

L3

L2

L1

H3

H2

H1

X3

X2

X1

C1

B1

A1

C2

B2

A2

C1(L3)

B1(L2)

A1(L1)

(L3)C2

(L2)B2

(L1)A2

L
I
N
E

L
O
A
D

CUSTOMER’S

3fl A.C. LINE

POWER

SUPPLY

EARTH GROUND
SEE NOTE 2

(G)

RF NOISE

FILTER

SEE NOTE 5

SEE NOTE 3

L3

L2

L1

T3

T2

T1

INPUT
AC DRIVE

OUTPUT

EARTH GROUND

SEE NOTE 1

SEE NOTES 3, 4

OUTPUT

REACTOR

OUTPUT

RFI FILTER

TO CASE

EARTH
GROUND
SEE NOTE 2

SEE NOTES 3, 4

SEE NOTES 3, 4

A.C. MOTOR

1

2

3

4

5

6

IN

OUT

T3

T2

T1

C1

B1

A1

C2

B2

A2

EARTH GROUND

SEE NOTE 2

SEE NOTE 6

DC

REACTOR

+ 1

+ 2

L31

L21

L11

NOTES

1.

Connect Drive ground terminal or panel to
earth ground. Always use low impedance
paths and connections.

2.

Mount input and output RFI filters physically
as close to the Drive as possible (on the
same panel, if possible). Filters should have
a solid connection from filter case or ground
terminal to Drive panel or ground terminal
(conduit with good bare metal to bare metal
connections may serve as the path). If
multiple input or output RFI filters are used,
they must be wired in parallel.

3.

Shield conductors with metallic conduit.

4.

Connect output conduit in a manner that
allows it to act as an unbroken shield from the
Drive panel to the motor casing.

5.

RF noise filter (different from RFI filter) part
no. 05P00325-0023 is a delta wye capacitor
network which is wired in parallel with the
Drive input terminals. On the smaller Drives
with die cast chassis, it must be mounted
externally. On the larger Drives with sheet
metal chassis, it may be mounted inside the
area where the input power wiring enters the
Drive. On units equipped with bypass, it may
be wired to the primary side of the circuit
breaker and mounted to the bypass panel or
sidewall.

6.

Connection points:

Drive w/o Bypass Drive w/ Bypass

Input

L1, L2, L3

Ckt Brkr L1, L2, L3

Output

T1, T2, T3

Unwired side of

Overload relay

IG.V7.01_new format.qxd:IG.V7.01_new format.qxd 8/21/07 2:24 PM Page 27