Drive parameter listing (n164-n179) – Yaskawa V74X Drives User Manual
Page 49

Drive Parameter Listing
(n164-n179)
Section 8
PARA-
SETTING RANGE
SETTING
FACTORY
USER
PARA.
METER
NAME
(AND UNITS)
INCREMENT
SETTING
SETTING
REF.
0:
Terminal FR (Voltage 0 - 10V)
1:
Terminal FR (Current 4 - 20mA)
2:
Terminal FR (Current 0 - 20mA)
n164
PID Feedback Selection
3:
Multi-Function Analog Input
1
0
5.28
(Voltage 0 - 10V)
4:
Multi-Function Analog Input
(Current 4 - 20mA)
5:
Pulse input
n166
Input Phase Loss
0 to 100 (%)
1%
0
1%
0
Detection Level
n167
Input Phase Loss
0 to 255 (sec)
1 sec
0
Detection Time
n168
Output Phase Loss
0 to 100 (%)
Detection Level
n169
Output Phase Loss
0.0 to 2.0 (sec)
0.1 sec
0
Detection Time
n173
DC Injection P Gain
1 to 999
1 (0.001)
83 (0.083)
n174
DC Injection I Time
1 to 250
1 (4ms)
25
(100ms)
n175
Reduce Carrier
0:
Disabled
at low speed selection
1:
Carrier Frequency reduced to 2.5kHz
1
0
5.5
when Fout <= 5Hz & Iout >= 110%
rdy : READY status
rdy
rEd: READ executes
rEd
n176
Digital Operator Parameter
Cpy: COPY executes
Cpy
rdy
5.29
Copy Function Selection
vFy: VERIFY executes
vFy
Sno
vA:
Inverter capacity display
vA
Sno: Software No. display
n177
Digital Operator
0:
Read disabled
Parameter copy
1:
Read allowed
1
0
5.29
Access Selection
n178
Fault History
(Note 3)
N/A
N/A
6.2
n179
Software Number
(Note 3)
N/A
N/A
4.4
Drive Parameters - Continued
Note 1: Factory setting differs depending on V7 capacity. See Appendix 3-1.
Note 2: Factory setting differs depending on control method selected (n002). See Appendix 3-1.
Note 3: n178 and n179 are display only parameters
Note 4: Parameter can be changed while V7 is operating.
49
IG.V7.01_new format.qxd:IG.V7.01_new format.qxd 8/21/07 2:24 PM Page 49