Interconnection Precautions
and Diagrams

Section 7

Notes for Figure 1-5 (2-Wire Control) and Figure 1-6 (3-Wire Control)

✱ – Indicates components not supplied.

– Main circuit terminal.

– Indicates control circuit terminal.

( ) – Indicates alternate terminal marking, i.e., (R) and L1.

▲ – Function labels shown for these terminals are determined by factory settings of

n050

through

n056

. (see TM.V7N.01)

● – Function labels shown for these terminals are determined by factory settings of

n057

through

n059

.

(see TM.V7N.01)

1.

Insulated twisted shielded wire is required.

2-conductor #18 GA. (Belden #8760 or equivalent).
3-conductor #18 GA. (Belden #8770 of equivalent).

Connect shield ONLY AT the Drive END (ground terminal ). Stub and isolate other end.

2.

+12V voltage output current capacity of control terminal FS is 20mA max.

3.

The Drive’s Electronic Thermal Overload function (n036, n037) meets standards set by UL and CUL for motor
thermal overload protection. If local code requires a separate mechanical overload protection, an overload relay
should be installed, interlocked with the Drive as shown. It should be the manual reset type to prevent automatic
restart following a motor fault and subsequent contact reclosure after cool down.

4.

Customer to connect terminal to earth ground.

5.

If the Digital Operator is used, remote operators, which duplicate functions of its command keys may not be
required. See Figure 4-1.

6.

For installation of Braking Resistor or Braking Resistor unit, refer to Appendix 6, “Dynamic Braking Option.”