Drive parameter listing (n005-n017) – Yaskawa V74X Drives User Manual

Page 37

Advertising
background image

37

Drive Parameter Listing

(n005-n017)

Section 8

PARA-

SETTING RANGE

SETTING

FACTORY

USER

PARA.

METER

NAME

(AND UNITS)

INCREMENT

SETTING

SETTING

REF.

n005

Stop Method

0:

Ramp to stop

1

0

5.24

1:

Coast to stop

n006

Reverse Prohibit

0:

Reverse Run enabled

1

0

1:

Reverse Run disabled

0:

STOP key is effective regardless of
programming of n003

n007

STOP Key Function

1:

STOP key is effective only when sequence

1

0

5.13

command (per n003) is from Digital Operator

0:

Frequency Reference from digital

n008

Reference Selection -

operator pot

1

0

5.13

Digital Operator

1:

Frequency Reference from n024

0:

ENTER key must be pressed to write-in

n009

Frequency Reference Setting

new value

1

0

5.13

Method From Digital Operator 1:

ENTER key does not have to be pressed
to write-in new value

Operation Selection

0:

Disabled (operation continues)

n010

When Digital Operator is

1:

Enabled (motor coasts to a stop and fault

1

0

5.15

Disconnected

is displayed)

n011

Frequency - Max.

50.0 to 400.0

0.1 (Hz)

60.0

n012

Voltage - Max.

0.1 to 255.0 (230V drive)

0.1 (V)

230.0

0.2 to 510.0 (460V drive)

460.0

n013

Frequency - Max.

0.2 to 400.0

0.1 (Hz)

60.0

Voltage Point

n014

Frequency - Midpoint

0.1 to 399.9

0.1 (Hz)

(Note 2)

5.27

n015

Voltage - Midpoint

0.1 to 255.0 (230V drive)

0.1 (V)

(Note 2)

0.2 to 510.0 (460V drive)

n016

Frequency - Min.

0.1 to 10.0

0.1 (Hz)

(Note 2)

n017

Voltage - Min.

0.1 to 50.0 (230V drive)

0.1 (V)

(Note 2)

0.2 to 100.0 (460V drive)

V7 Parameters - Continued