Output amps, carrier and overload comparison, 240v heavy duty ratings (c6-01=0), 480v heavy duty ratings (c6-01=0) – Yaskawa GPD 515/G5 to F7 User Manual

Page 20

Advertising
background image

Product Transition Guide
Appendix 1 –Amps, Carrier , Overload, Dimensions, Heat Loss

____________________________
PL.F7.02.TransitionGuide 6/5/06
Page 20 of 40
Yaskawa Electric America, Inc

Output Amps, Carrier and Overload Comparison
240V Heavy Duty Ratings (C6-01=0)

240V F7 “Heavy Duty” Setting (C6-01=0)

F

F

7

7

GPD515/G5 Model

NEC

HP

240V

NEC

Amps

F7

Model

CIMR-

F7U

Output

Amps

Heavy

Duty

Fc

kHz

Heavy

Duty

Overload

%

Heavy

Duty

GPD515/G5

Model CIMR-

G5U

Output

Amps

Fc

kHz

OL %

0.5 2.2

0.75 3.2

20P41

3.2 2 150

0.75 3.2 20P71 4.1 2 150

20P41

3.2 15 150

1 4.2

1.5 6

20P71

6 15

150

2 6.8

21P51

7 2 150

21P51

8 15

150

3 9.6

22P21 9.6 2 150

3 9.6

23P71 15 2 150

22P21

11 15

150

5 15.2

23P71 17.5 15 150

7.5 22

25P51

23 2 150

25P51

25 15

150

10 28 27P51 31 2 150 27P51

33 15

150

15 42 20111 45 2 150 20111

49 15

150

20 54 20151 58 2 150 20151

64 15

150

25 68 20181 71 2 150

30 80 20221 85 2 150

20181

80 15

150

40 104 20301 115 2 150

50 130 20370 145 2 150

20301

130 10 150

60 154 20450 180 2 150 20371

160 10 150

75 192 20550 215 2 150 20551

224 10 150

100 248 20750 283 2 150 20751

300 10 150

125 312 20900 346 2 150 20900

358 2 150

150 360

150

360

21100

415

2

120

(1)

21100 415 2 150

(1)

Heavy Duty overload current rating for model no. 21100 is 120% of rated output current for 60

seconds.