Yaskawa GPD 515/G5 to F7 User Manual

Page 30

Advertising
background image

Product Transition Guide
Appendix 2- Parameter Differences

____________________________
PL.F7.02.TransitionGuide 6/5/06
Page 30 of 40
Yaskawa Electric America, Inc


GPD515/G5 Parameters

F7 Parameters

Parameter

No.

Name

(DigitalOperator

Display)

Setting or Selection

Parameter

No.

Name

(Digital Operator Display)

Remarks on

Setting or Selection

d6-03

Magnetic Field Forcing
Function Selection

New Parameter
0:Disabled
1:Enabled

E1-02

Motor Selection

0:Std Fan-Cooled
1:Std Blower-Cooled
2:Vector Motor

L1-01

Motor Overload
Protection Selection

Changed Parameter No.
Additional selection
0: Disabled
1: Standard Fan Cooled
2: Standard Blower Cooled
3: Vector Motor

E2-11

Motor Rated Output

New Parameter
This value is automatically set
during auto tuning.

E4-01

Motor 2 Max. Output
Frequency

E3-02

Motor 2 Maximum
Output Frequency

Changed Parameter No.

E4-02

Motor 2
Max.Voltage

E3-03

Motor 2 Maximum
Output Voltage

Changed Parameter No.

E4-03

Motor 2 Max.
Voltage Frequency
Base Frequency

E3-04

Motor 2 Base
Frequency
Base Frequency

Changed Parameter No.

E4-04

Motor 2 Mid.
Output Frequency 1
Mid Frequency

E3-05

Motor 2 Mid Output
Frequency
Mid Frequency

Changed Parameter No.

E4-05

Motor 2 Mid.
Output Frequency
Voltage 1
Mid Voltage

E3-06

Motor 2 Mid Output
Voltage VA
Mid Voltage

Changed Parameter No.

E4-06

Motor 2 Min.
Output Frequency
Min Frequency

E3-07

Motor 2 Minimum
Output Frequency
Min Frequency

Changed Parameter No.

E4-07

Motor 2 Min.
Output Frequency
Voltage
Min Voltage

E3-08

Motor 2 Minimum
Output Voltage
Min Voltage

Changed Parameter No.

E5-01

Motor 2 Rated
Current

E4-01

Motor 2 Rated Current Changed Parameter No.

E5-02

Motor 2 Rated Slip

E4-02

Motor 2 Rated Slip

Changed Parameter No.

E5-03

Motor 2
No-load Current

E4-03

Motor 2 No-Load
Current

Changed Parameter No.

E5-04

Motor 2
Number of poles

E4-04

Motor 2 Number of
Poles

Changed Parameter No.

E5-05

Motor 2 Line-to-line
Resistance

E4-05

Motor 2 Line-to-Line
Resistance

Changed Parameter No.

E5-06

Motor 2 Leak
Inductance

E4-06

Motor 2 Leakage
Inductance

Changed Parameter No.

E4-07

Motor 2 Rated Output

New Parameter
This value is automatically set
during auto-tuning.

F4-07

AO-12 Channel 1
Signal Level

New Parameter
Sets the range of the voltage
output.
0: 0 to 10 Vdc
1: -10 to +10 Vdc

F4-08

AO-12 Channel 2
Signal Level

New Parameter
Sets the range of the voltage
output.
0: 0 to 10 Vdc
1: -10 to +10 Vdc