Product Transition Guide

Appendix 2- Parameter Differences

____________________________

PL.F7.02.TransitionGuide 6/5/06

Page 29 of 40

Yaskawa Electric America, Inc

GPD515/G5 Parameters

F7 Parameters

Parameter

No.

Name

(DigitalOperator

Display)

Setting or Selection

Parameter

No.

Name

(Digital Operator Display)

Remarks on

Setting or Selection

C6-01

Drive Duty Selection

New parameter
0: Heavy Duty
1: Normal Duty 1
2: Normal Duty 2

C6-02

Carrier Frequency
Selection

New parameter function
different than old C6-02 in
GPD515/G5

0: Low noise
1: Fc = 2.0 kHz
2: Fc = 5.0 kHz
3: Fc = 8.0 kHz
4: Fc = 10.0 kHz
5: Fc = 12.5 kHz
6: Fc = 15.0 kHz
F: Program Determined by the
settings of C6-03 thru C6-05

C6-01

Carrier Frequency
Upper Limit

C6-03

Carrier Frequency
Upper Limit

Changed Parameter No.

C6-02

Carrier Frequency
Lower Limit

C6-04

Carrier Frequency
Lower Limit

Changed Parameter No.

C6-03

Carrier Frequency
Proportional Gain

C6-05

Carrier Frequency
Proportional Gain

Changed Parameter No.

C7-01

Hunting Prevention
Selection

0:Disabled
1:Enabled

n1-01

Hunting Prevention
Selection

Changed Parameter No.

C7-02

Hunting Prevention
Gain

n1-02

Hunting Prevention
Gain Setting

Changed Parameter No.

C8-08

AFR Gain

n2-01

Speed Feedback
Detection Control AFR
Gain

Changed Parameter No.

C8-09

AFR Time Constant

n2-02

AFR Time

Changed Parameter No.

n2-03

Speed Feedback
Detection Control
AFR Time Constant 2

New parameter
Sets the time constant to
control the amount of change
in the speed at low speed.

d1-09

Frequency Reference 9 New Parameter

d1-10

Frequency Reference
10

New Parameter

d1-11

Frequency Reference
11

New Parameter

d1-12

Frequency Reference
12

New Parameter

d1-13

Frequency Reference
13

New Parameter

d1-14

Frequency Reference
14

New Parameter

d1-15

Frequency Reference
15

New Parameter

d1-16

Frequency Reference
16

New Parameter

D1-09

Jog Frequency
Reference

d1-17

Jog Frequency
Reference

Changed Parameter No.

d2-03

Master Speed
Reference Lower Limit

New Parameter

d6-01

Magnetic Field
Weakening Level

New Parameter

d6-02

Magnetic Field
Frequency

New Parameter