Yaskawa GPD 515/G5 to G7 User Manual

Page 27

Advertising
background image

Product Transition Guide

Appendix 2- Parameter Differences

____________________________

PL.G7.02.TransitionGuide 4/21/04

Page 27 of 38

Yaskawa Electric America, Inc

GPD515/G5 Parameters

G7 Parameters

Parameter

No.

Name

(DigitalOperator Display)

Setting or Selection

Parameter

No.

Name

(Digital Operator Display)

Remarks on

Setting or Selection

— —

F5-03

DO-08 Channel 3 Output
Selection

New Parameter

— —

F5-04

DO-08 Channel 4 Output
Selection

New Parameter

— —

F5-05

DO-08 Channel 5 Output
Selection

New Parameter

— —

F5-06

DO-08 Channel 6 Output
Selection

New Parameter

— —

F5-07

DO-08 Channel 7 Output
Selection

New Parameter

— —

F5-08

DO-08 Channel 8 Output
Selection

New Parameter

— —

F5-09

DO-08 Output Mode
Selection


New Parameter
0:8-channel individual outputs.
1:Binary code output.
2:Output according to
F5-01 to F5-08 settings.

F9-02 Option External Fault

Detection Selection

0:Always Detected
1:Only During Run

F6-02

Option External Fault
Detection Selection

Changed Parameter No.

F9-03 Option External Fault

Detection Operation
Selection

0: Ramp to Stop
1: Coast to Stop
2: Fast - Stop
3: Alarm Only

F6-03

Option External Fault
Detection Operation
Selection

Changed Parameter No.

F9-04 Trace Sampling Time

F6-04

Trace Sampling from
Communications Option
Board

Changed Parameter No.

TorqueReference/

F9-05

Torque Limit Selection
through DP-RAM
communication

0: Disabled
1: Enabled

F6-06

Torque Reference/Torque
Limit Selection through
DP- RAM communication

Changed Parameter No.

F9-06 DP-RAM Communication

Error Detection Operation
Selection

0:Ramp to Stop
1:Coast to Stop
2:Fast - Stop
3:Alarm Only

F6-01

DP-RAM Communication
Error Detection Operation
Selection

Changed Parameter No.