Product Transition Guide

GPD515/G5 to G7

GPD515/G5 Parameters

G7 Parameters

Parameter

No.

Name

(DigitalOperator

Display)

Setting or Selection

Parameter

No.

Name

(Digital Operator Display)

Remarks on

Setting or Selection

O1-05

Parameter No.
Display Selection
Address Display

0:Parameter Number
1:Memobus Address

o1-05

LCD Brightness
Adjustment

Modified function:
Sets the contrast of the digital
operator LCD. A set ting of
“1” is the lightest contrast and
a setting of “5” is the darkest
contrast.

o2-10

Cumulative CoolingFan
Operation Time Setting

New parameter

o2-12

Fault Trace/Fault
History Clear Function

New parameter
0: Disabled no effect.
1: Enabled - resets U2 and U3
monitors, and returns o2-12 to
zero.

o2-14

kWh User Monitor
Initialization

New parameter
0: Disabled no change.
1: Enabled - Resets U1-29 to
zero and returns o2-14 to zero.

o3-01

Copy Function
Selection

New parameter
0: COPY SELECT no
function
1: INV -> OP READ - All
parameters are copied from
the Drive to the digital
operator.
2: OP -> INV WRITE - All
parameters are copied from
the digital operator to the
Drive.
3: OP<-->INV VERIFY -
Parameter settings in the Drive
are compared to those in the
digital operator.
NOTE: When using the copy
function, the Drive model
number o2-04, software
number U1-14, and control
method A1-02 must match or
an error will occur.

o3-02

Copy Allowed
Selection
Read Allowable

New parameter
0: Disabled - No digital
operator copy functions are
allowed.
1: Enabled - Copying allowed



PL.G7.02.TransitionGuide 4/21/04
Page 36 of 38