Soft charge resistor/contactor – Yaskawa GPD 506/P5 Section One User Manual

Page 22

Advertising
background image

PP.P5G5.01.Troubleshoot

Page 22

Rev. 06/11/2003

Soft Charge Resistor/Contactor

for 18kW through 160kW models

After the 230V contactor has energized, an “answer back” auxiliary

contact closes. When this contact is closed, the control board

receives a signal indicating that the soft charge contactor has

energized. If the control board does not receive this signal, the

inverter will not operate and an undervoltage fault will be displayed on

the digital operator.

Soft charge resistor

Soft charge contactor

Advertising
This manual is related to the following products: