Control power fuse – Yaskawa GPD 506/P5 Section One User Manual

Page 42

Advertising
background image

PP.P5G5.01.Troubleshoot

Page 42

Rev. 06/11/2003

Control Power Fuse

for models 18kw through 160kW

All Yaskawa GPD 506/P5 and GPD 515/G5 inverters have a control

power fuse. The fuse is located on either the gate drive board (2PCB)
or the power supply board (3PCB). If the fuse is located on the gate
drive board (2PCB), it will be soldered to the board. If the control
power fuse is open, then the gate drive board may be defective. On
the larger inverter models, the fuse is a “plug in” type.

The fuse can easily be checked using an ohmmeter set to the R X 1

scale. Place one lead of the ohmmeter on one side of the fuse, and
place the other lead of the ohmmeter on the other side of the fuse. If
the fuse is bad, the measured value will be infinite ohms.

Power Supply Board

(3PCB)

Solder type

Plug in type

Gate Drive Board

(2PCB)

Advertising
This manual is related to the following products: