Output transistor check – Yaskawa GPD 506/P5 Section One User Manual

Page 38

Advertising
background image

PP.P5G5.01.Troubleshoot

Page 38

Rev. 06/11/2003

Test Equipment - Analog Ohmmeter Set to R X 1 Scale

or Digital Multimeter set to the Diode Check.

Step

Approximately

0.5 Volts

Ohmmeter

Positive Lead

Ohmmeter

Negative Lead

1

2

3

4

T1, T2, T3 Terminals Terminal labeled (+)

Approximately

4 Ohms

Terminal labeled (-)

Infinite Ohms

0L displayed

Terminal labeled (-)

Approximately

4 Ohms

Approximately

0.5 Volts

Terminal labeled (+)

Infinite Ohms

0L displayed

Expected

Reading

(Analog Meter)

Expected

Reading

(Digital Meter)

T1, T2, T3 Terminals

T1, T2, T3 Terminals

T1, T2, T3 Terminals

Voltage

Model

Connector (-) DC bus (+) DC bus

230V

18kW & 22kW

19CN

Pin 1

Pin 5

30kW ~ 75kW

26CN

Pin 5

Pin 1

460V

18kW ~ 45kW

19CN

Pin 1

Pin 5

55kW ~ 160kW

26CN

Pin 5

Pin 1

Output Transistor Check

for models 18kw through 160kW

For GPD 506/P5 inverters, refer to the following connectors for a test point for the

(-) DC bus and (+) DC bus.