Yaskawa MP2000iec Series User Manual

Page 4

Advertising
background image

MP2000iec Series QRG Rev 3.3

1.5 Login to Webserver

KEY INFORMATION

Step

Description

Detail

1

Establish ethernet
communication with controller

See procedure 1.4 - type controller IP address into Internet Explorer to open the
controller's built in webserver.

2

Enter Login Credentials

Login:

Admin

(case sensitive).

Password:

MP2300S

(all caps, for MP2300Siec and MP2310iec).

Password:

MP2600

(all caps, for MP2600iec).

Password:

MP3200

(all caps, for MP3200iec)

Troubleshoot

The login configuration may have been customized. Obtain the login information
from the network administrator. Otherwise, the controller may be reset to factory
default using Motionworks IEC. See procedure __

1.6 Set IP Address of Controller

KEY INFORMATION

Step

Description

Detail

1

Login to Webserver

See Procedure. Login: Admin. Password: MP2300S, MP2600, MP3200, MP3300

2

Open "Ethernet Config"

On the left side

3

Set IP address

Select "Ethernet Config". Enter IP address and Subnet Mask. Click "Update Built-in
Ethernet Settings" to save.

4

Set default gateway

Select "Ethernet Config". Enter Default Gateway. If not gateway device exists on
the network, enter the same address as the IP address. Click "Update Built-in
Ethernet Settings" to save.

5

Turn off E-INIT switch

E-INIT must be off for configured ethernet settings to take effect at next reboot. If E-
INIT is left on, the address will be 192.168.1.1 regardless of the Ethernet Config
settings.

6

Reboot Controller

Under "Maintenance" -> reboot, then "Reboot Controller" and "OK" to confirm. Wait
45 seconds for reboot. The settings do not take effect until the controller is
rebooted with E-INIT off.

1.7 Update firmware

KEY INFORMATION

Do NOT update firmware in the field unless directed by Yaskawa.
DO update firmware before code development begins on new application.

Step

Description

Detail

1

Establish ethernet
communication with controller

See procedure 1.4 - type controller IP address into Internet Explorer to open the
controller's built in webserver.

2

Determine current firmware
version

The webserver welcome page lists the firmware version number, build number, and
build date

3

Acquire a firmware zip file

yaskawa.com/iecfw to download firmware files. Must log in to yaskawa.com

4

Login to Webserver

See Procedure. Login: Admin. Password: MP2300S, MP2600, MP3200, MP3300

5

Stop all motion

Operate the machine according to existing program.

6

Enable supervisor mode

Under "Maintenance" -> "Update Firmware", then click "enabled via software" and
"reboot controller". Wait 45 seconds for reboot.

7

Load firmware zip file

Under "Maintenance" -> "Update Firmware", then browse for firmware file, and
"upload". Upload takes about 1 minute. Do not attempt to unzip the firmware file.

8

Update firmware

Confirm the update version. Then click "update" button. The update takes about 2
minutes. Do not use the controller during this time.

9

Reboot Controller

Under "Maintenance" -> reboot, then "Reboot Controller" and "OK" to confirm. Wait
45 seconds for reboot.