GENERAL OPERATION

11

MicroTrac to PLC

12/22/94- RD 3196-10

MicroTrac to
PLC (LOGO)

Logic outputs from a PAC schematic to a PLC can be visualized as shown in
Figure 4. Logic output (LOGO) PAC blocks send a logic value from the drive
to the remote device specified by the node, channel, and sub channel defined
for that block. The node number for a single PLC gateway is typically 200.
These logics utilize groups 1-7 for a maximum total of 112 (7 x 16) MicroTrac
to PLC logic bits.

The LAN channel number is in octal notation and corresponds directly with
the A-B PLC rack and group number for the associated simulated A-B input.
In addition, the number will have a 100's prefix digit of 1 that can be
associated with the A-B PLC input "I" notation. Thus:

LAN CHANNEL 124 = INPUT RACK 2, GROUP 4 or I:24
LAN CHANNEL 127 = INPUT RACK 2, GROUP 7 or I:27

The sub channel number will also be in octal, and will directly correspond to
the bit number of the simulated output. Thus, the 16 possible bits are:

LAN SUB CHANNEL 00 = BIT 00

: :

:

LAN SUB CHANNEL 07 = BIT 07
LAN SUB CHANNEL 10 = BIT 10

: :

:

LAN SUB CHANNEL 17 = BIT 17

Each PLC logic input bit can be addressed by no more than one drive. If more
than one drive attempts to initialize the same bit (sub channel) in a given
group, a “Logic Output Allocation Error” message will be sent to the drive
over the LAN.

NOTE: LAN traffic throughput may significantly improved if all logic
values for a particular drive are grouped together and not needlessly
divided between multiple PLC groups.

Figure 4. PAC Logic Output to PLC

TYPICAL LOGO

103-D

LOGO

Node Chan. Sub

200 136 3

LAN Cable

Logic Bits

PLC Gateway

Remote

I/O Cable

PLC Ladder

Logic

I:36/03