GENERAL OPERATION

13

MicroTrac to PLC

5/2/95- RD 3196-10

MicroTrac to
PLC (NUMO)

Numeric outputs from a PAC schematic to a PLC can be visualized as shown in
Figure 6. Numeric output (NUMO) PAC blocks send a numeric value from the
drive to the remote device specified by the node, channel, and sub channel defined
for that block. The node number for a single PLC gateway is typically 200.

The channel number here has a similar meaning to that discussed above for the
logic function, except that the leading digit must be a 1. The SmartMUX board
only supports Numeric block transfers to slot 0 and group 0. Thus:

LAN CHANNEL 130 = RACK 3, GROUP 0

The PAC block’s sub channel number will be in decimal, and will normally range
from 0 through 63. This number represents the location of the numeric output data
in the Block Transfer Read data file. Up to 64 values may be processed in one
Block Transfer operation.

Every numeric value exchanged between the drive system and the PLC must have
a unique value for channel and subchannel.

Figure 6. PAC Numeric Output to PLC

TYPICAL NUMO

104-D

NUMO

Node Chan. Sub.

200 110 19

LAN Cable

DATA

PLC Gateway

Remote

I/O Cable

PLC Ladder

Logic

FF

Block

Transfer

Read